Considering a Utility-Centric Framework Based on "Minimum Orthophosphate" Criteria for Mitigation of Elevated Cuprosolvency in Drinking Water.

Rebecca B KrissEmily SmithGrace ByrdMichael SchockMarc A Edwards
Published in: Environmental science & technology (2024)
Gaps in the United States Environmental Protection Agency (US EPA) Lead and Copper Rule (LCR) leave some consumers and their pets vulnerable to high cuprosolvency in drinking water. This study seeks to help proactive utilities who wish to mitigate cuprosolvency problems through the addition of orthophosphate corrosion inhibitors. The minimum doses of orthophosphate necessary to achieve acceptable cuprosolvency in relatively new copper pipe were estimated as a function of alkalinity via linear regressions for the 90th, 95th, and 100th percentile copper tube segments ( R 2 > 0.98, n = 4). Orthophosphate was very effective at reducing cuprosolvency in the short term but, in some cases, resulted in higher long-term copper concentrations than the corresponding condition without orthophosphate. Alternatives to predicting "long-term" results for copper tubes using simpler bench tests starting with fresh Cu(OH) 2 solids showed promise but would require further vetting to overcome limitations such as maintaining water chemistry and orthophosphate residuals and to ensure comparability to results using copper tube.