Login / Signup

Respiratory Symptoms and Skin Sick Building Syndrome among Office Workers at University Hospital, Chiang Mai, Thailand: Associations with Indoor Air Quality, AIRMED Project.

Vithawat SurawattanasakulWachiranun SirikulBianca BrijnathKampanat WangsanJinjuta PanumasvivatPheerasak AssavanopakunSupang Muangkaew
Published in: International journal of environmental research and public health (2022)
Sick building syndrome (SBS) is the term used to describe the medical condition in which people in a building suffer from symptoms of illnesses for no apparent reason. SBS was found to be associated with indoor air quality (IAQ) but there are a variety of determinants (buildings, in particular). Identifying and controlling factors related to SBS is crucial for improving worker health and efficiency. A cross-sectional study was conducted to investigate (1) the prevalence of respiratory symptoms and skin SBS and (2) their associations with IAQ among office workers in administrative offices in an academic medical institute. A self-reporting questionnaire assessing the worker's characteristics, working conditions, and perception of working environments was used. The building assessment was via a walk-through survey and IAQ measurement. Of 290 office workers, 261 (90%) in 25 offices of 11 buildings took part in the survey. The highest prevalence of SBS was nasal symptoms (25.3%). We found that to reduce the risk of SBS, optimal air temperature levels in air-conditioned offices should be lower than 23 °C, with relative humidity between 60% and 70%. Lowering indoor CO 2 levels below 700 ppm may be indicative of adequate ventilation to prevent SBS by reducing worker discomfort and indoor contaminants (e.g., formaldehyde).
Keyphrases